2) pressure test
耐压试验
1.
Pressure Test of Pressure Vessel in Refrigeration Equipment;
制冷装置中压力容器的耐压试验
2.
Discussion on pressure test methods for vertical vessels;
直立容器耐压试验方法探讨
3.
Pressure test in periodical examination of pressure vessel;
压力容器定期检验中的耐压试验
3) withstanding voltage test
耐压试验
1.
A preventive withstanding voltage test of cable was made for guaranteeing the power supply for an important international meeting.
通过对某10kV电缆进行预防性耐压试验,发现电缆的绝缘存在缺陷。
2.
This paper sets forth the disadvantages of DC withstanding voltage test of cross-linked power cable,the method of AC withstanding voltage test(focused on the principle and advantage of series resonant withstanding voltage test method),the standard of AC withstanding voltage test,the application and caution of resonant power products.
通过列举交联电缆直流耐压试验的缺点、电缆交流耐压试验方法(重点以串联谐振耐压试验的基本原理、方法、优点为例)、介绍交流耐压试验标准、谐振电源产品应用实例和使用注意事项,对电力电缆的耐压试验方法做了些许浅显论述,探讨了变频谐振方法在交联电缆现场交流耐压中的效果和可行性。
4) withstand voltage test
耐压试验
1.
Study on feasibility using resonance device to do AC withstand voltage test of large-capacity machine;
论使用谐振装置对大电机交流耐压试验的可行性
2.
The paper summarizes DC withstand voltage test,ultra-low frequency withstand voltage test,oscillation wave voltage test and variable frequency vibration test.
概述了XLPE电缆的直流耐压试验、超低频耐压试验、振荡波电压试验和变频谐振试验,提出了直流耐压试验存在的问题,对运行过的电缆不再推荐做直流耐压试验,指出了超低频0。
3.
The current withstand voltage test methods to XLPE power cable in detail was summarized.
对XLPE交联聚乙烯电力电缆的耐压试验方法作了总结,并根据宝钢电力电缆安装后现场试验的做法和问题,结合国内外现行的不同标准,论述了变频谐振试验在宝钢交联电力电缆的应用效果,给出了进一步研究的建议。
5) voltage withstand test
耐压试验
1.
Analysis on using variable-frequency series-resonant voltage withstand test;
浅析变频串联谐振耐压试验的应用
2.
It is verified that the BPD frequency conversion power definitely can be used not only in resonance voltage withstand test of large capacity equipment for example electric cables and GIS,but also in partial discharge test of transformer.
介绍了某供电公司对主变局放和谐振耐压试验电源的研究和选用思路,简要介绍了局放和耐压试验现场实施情况,证实了BPD型变频电源不仅可以用于GIS及电缆等大容量设备的谐振耐压试验,而且可以用于变压器的局部放电试验。
3.
This paper expatiates on the different methods and contents of acceptance and preventive tests of 6~10 kV and 35 kV XLPE cables, indicating the defects in conventional DC voltage withstand test and recommending variable~frequency series~resonant test for the acceptance and preventive tests of XLPE cables.
并指出传统的直流耐压试验存在不足之处,对交联聚乙烯绝缘电缆的交接和预防性试验应优先采用变频率串联谐振试验。
6) high voltage test
耐压试验
1.
The high voltage test of electrical system shall be done to protect the running of equipment and to avoid the equipment failure.
绝缘电阻和吸收比试验、泄漏电流和直流耐压试验以及介质损失角测量试验等虽然能发现很多绝缘缺陷,但因其试验电压低于被试品的工作电压,往往对一些绝缘缺陷还不能及时发现,为了进一步暴露设备缺陷、检查电气设备绝缘水平和是否能投入运行,有必要进行耐压试验。
补充资料:耐压试验
耐压试验
voltage withstand tests
冲击耐压试验按施加的冲击电压性质又可分为雷电冲击耐压试验和操作冲击耐压试验。雷电冲击耐压试验又有全波冲击和截波冲击两种。冲击耐压试验是用于考验设备耐受雷电波和操作波的能力。由于试验技术复杂,仅在型式试验或某些超高压重要设备的出厂试验中进行。冲击试验电压由冲击电压发生器提供,对于变压器类产品也可以采用向低压侧放电使高压侧感应出所需的操作被冲击试验电压。 直流耐压试验对直流设备或有直流分量的整流设备,必须用短时间直流耐压试验来考验绝缘强度。有些交流设备,例如电力电缆和发电机,由于电容值很大,采用直流耐压试验可使试验设备容量减小,适合于交接试验和运行设备的预防性试验。直流电压下绝缘中的电场分布和交流下是很不相同的,两种试验不能完全等效。直流耐压试验对发现贯穿性缺陷比较有效。no一yo sh一yo一,耐压试验(voltage withstand tests)按规定的加压方式对电气设备或绝缘结构施加规定电压以考验其耐受电压能力的试验。耐压试验以试品不被击穿或闪络作为通过试验的主要判据。由于施加电压较高,在绝缘中某些地方会出现较高的电场强度致使绝缘有可能造成局部损伤,因此它是一种破坏性绝缘试验。 耐压试验的种类及施加电压水平,由被试产品或绝缘结构所处运行电压等级的绝缘配合来确定。它应该对运行中可能出现的过电压状态进行考核。由于试验只能是短时间的或者是次数有限的,因此试验水平必须高于过电压水平,以保证有足够的安全裕度。耐压试验按施加电压的种类可分为交流耐压试验、冲击耐压试验和直流耐压试验。 交流耐压试验通常称为一分钟工频耐压试验,因为此项试验在多数情况下是采用50Hz(某些国家用60Hz)正弦交流电压,在规定的电压值下持续时间为1 min。交流耐压试验按试验电压的取得方式有外施耐压试验和感应耐压试验两种。外施耐压试验是由试验变压器或其他装置提供试验电压,直接施加在与被试端子相连的全部金属电极上。感应耐压试验由于电压较高,为避免铁芯中的磁饱和,需采用频率高于工频的交流电压,施加电压的时间应按规定缩短。对电容量较大的试品也有采用频率很低的交流电压(例如。.IHz),施加的电压值应有所增加。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。