您的位置:首页 -> 词典 -> 直流耐压试验
1)  DC withstand voltage test
直流耐压试验
1.
The HVDC withstand voltage test can discover the defect of paper insulated cable efficiently, but it has limitation in discovering the defect of cross-linked polyethylene insulated power cable.
分析了高电压直流耐压试验可有效发现纸绝缘电缆缺陷,但在发现交联聚乙烯绝缘电力电缆缺陷方面有局限性。
2)  DC voltage withstand test
直流耐压试验
1.
In order to summarize the law of on-site DC voltage withstand test of ±800 kV DC equipment,and to provide a reference for similar test and research,the first on-site DC voltage withstand test of ±800 kV DC equipment in ± 800 kV DC transmission project of China was introduced,and the test scheme and test data were analyzed.
为了总结±800kV特高压设备现场直流耐压试验规律,为以后类似试验及研究提供参考,介绍了首次在国内某±800kV工程某换流站进行的±800kV特高压设备现场直流耐压试验,分析了试验方案的确定过程和试验数据,并用两种模型的最小二乘法对试验数据进行拟合,得出±800kV特高压设备直流耐压试验的伏安特性,发现它比较符合二次多项式函数,并且非线性强电晕的起始电压约为400kV。
3)  DC testing of cables
电缆直流耐压试验
4)  ac voltage withstand test
交流耐压试验
1.
The new demands of IEC standard for XLPE cable and the status of AC voltage withstand test on XLPE cable;
交联电缆技术要求的新趋势及交流耐压试验的状况
2.
This article from the concept of the crosslinked polyethylene cable,introduced the limitations of the widely-used XLPE cable conventional tests,proposed the method and the advantages of AC voltage withstand test.
本文从交联聚乙烯电缆的概念出发,介绍了被广泛使用的交联聚乙烯电缆采用常规试验的局限性,同时提出了采用交流耐压试验的方法及优点,以国外的相关试验标准作为参考,建议我国尽快拿出自己的试验标准并予以推广。
5)  AC voltage withstanding test
交流耐压试验
1.
In this paper,radical AC voltage withstanding tests and partial discharge (PD) detection are discussed.
阐述了进行气体绝缘组合电器(GIS)现场交流耐压试验的基本方法,并对局部放电检测诊断内部绝缘的方法进行了讨论。
2.
In this paper, the methods of AC voltage withstanding test and PD detection are generally discussed.
阐述了对GIS进行现场交流耐压试验的基本方法,并讨论了传统的局部放电测量方法,综合分析GIS现场绝缘试验的有效性和存在的问题,指出交流耐压试验配合灵敏的局放测量是有效的现场试验方法。
6)  AC withstand voltage test
交流耐压试验
1.
The fault of AC withstand voltage test for 35kV power transformer are intro-duced.
介绍了一台35kV电力变压器交流耐压试验故障情况,分析了故障原因,并提出了预防措施。
2.
In order to ensure the commissioning and safety operation of 750 kV power transmission and transformation project, and exclude the hidden danger that may exist during high-voltage electrical equipment installation, the causes of gas-insulated failure of 800 kV GIS circuit breakers were analyzed, which happened in AC withstand voltage tests.
为保证750kV超高压输变电工程顺利投运和安全运行,排除高压电气设备安装中可能存在的隐患,对800kV气体绝缘(GIS)断路器现场交流耐压试验中发生的气体绝缘破坏原因进行分析,根据检测、分析,逐步排除,认定导电性异物浮游到屏蔽罩表面是造成绝缘破坏的原因,提出制作全密封式防尘棚、完善出厂和现场质量检查工艺及常规试验后分合50次重新进行内检等措施,以供将来日渐增多的变电站调试和运行维护参考。
补充资料:操作冲击感应耐压试验


操作冲击感应耐压试验
inductive withstanding test with switching impulse

COOzuoch。门gJ}90自yingnolyoshjyo门操作冲击感应耐压试验(induetivo with-standing test with switehing impulse)在电力变压器低压绕组施加操作冲击电压,通过电磁感应使变压器高压绕组的绝缘经受过电压考验的试验。试验所施加的电压波形是模拟电力系统内部由于开关操作或发生故障产生的一种波形,称为操作冲击电压波。根据中国电力行业标准的规定,操作冲击感应耐压试验可应用在变电所现场,对电力变压器进行绝缘考验。由于这种耐压方式省去了大容量的供电变压器,试验装备上可比采用三倍频试验装置施加正弦波电压更为方便。在电力变压器制造厂,对额定电压为3 30 kV及以上电压等级的电力变压器应该进行操作冲击耐压试验。此时,也可采用感应耐压方式。 试验电压波形对变压器类设备(包括互感器以及电抗器)内绝缘所使用的标准操作冲击电压波形如图1所示。Um为电压峰值,Tl为视在波前时间,TZ为 礁电)。9之J’盯0.3到南┌─┬───┐│尹│泣互军│└─┼───┤ │T2 │ └───┘图1内绝缘试验用的标准操作冲击电压波形由视在原点起算到第一次过零时间,T3为90%峰值电压持续时间。规定T3不小于200娜;孔不小于500件s;IEC76一3文件规定Tl不小于20娜,通常不大于250拜S;中国国家标准规定Tl为20一25。尸匀中国电力行亚标准规定Tl不小于20拜S。上述波形与外绝缘耐压和放电所采用的波形有所区别。试验电压波的极性规定为负极性。试验电压峰值u~由有关标准规定。施加的操作冲击电压的次数为三次。 原理接线该试验的原理接线见图2。由直流充电的电容C,,经一对铜球间隙FA放电,向变压器T低压侧施加一操作波。变压器高压侧因电磁感应,按变比升高电压产生试验用的操作波形。调节电图2试验的原理接线阻R:、R:及电容CZ可调节变压器低压侧操作波至合适形状,其高压侧除初始阶段外,波形基本上与低压侧相同。过零时间TZ除与C:电容量有关外,很大程度上取决于变压器非线性的励磁电抗大小,因此与铁芯的饱和程度、剩磁的大小及极性相关。