说明:双击或选中下面任意单词,将显示该词的音标、读音、翻译等;选中中文或多个词,将显示翻译。
您的位置:首页 -> 词典 -> 通断能力试验
1)  making-breaking capacity test
通断能力试验
1.
On the basis of introducing the characteristics and effect of virtual instruments and sensors in brief, a new measurement method of accomplishing making-breaking capacity test of switching apparatus by using virtual instruments and sensors was brought forward, and the test circuit was also introduced.
在简要介绍虚拟仪器和传感器的特点和作用的基础上,提出了一种利用虚拟仪器和传感器完成开关电器通断能力试验电气参数测量的新方法,并对试验线路进行了介绍。
2)  lab constriction of AC on-off ability
交流通断能力试验室
3)  breaking capacity test/triggered vacuum switch
通断能力试验/真空触发开关
4)  on-off test
通断试验
1.
short-circuit),AC on-off test is simulated in the short-circuit conditions to check reliability of electric switches.
矿用防爆电气开关在非正常条件下(例如短路)也应能接通或分断电流,交流通断试验就是在模拟的短路系统状态下进行,以考核开关电器的可靠性。
5)  make-break capacity
通断能力
1.
Exemplified by contactor,this paper recomends a PLC′s control system of make-break capacity of low-voltage electric apparatus and explains the PLC′s application by ladder diagrams.
本文以接触器为例 ,介绍了一种低压电器通断能力 PL C控制系统的电气线路 ,并用梯形图对 PL C的应用做了说明。
6)  breaking test
破断力试验
补充资料:开断能力试验
      在规定条件下检验开关设备能够开断预期开断电流的性能的试验。不同的开关电器要求的开断电流有很大的差别。例如,断路器和熔断器要求具有开断几千安、几十千安短路电流的能力,而负荷开关只要求开断额定电流或几倍额定电流。但是它们的开断能力试验方法和要求大致相同。
  
  以高压断路器为例,三极断路器应能关合、开断所有的短路电流,包括对称的及非对称的,直到额定短路开断电流。如果断路器在最高电压下关合和开断所规定的10%、 30%、60%和100%额定三相对称和非对称短路电流,则证明断路器已具备开断所有短路电流的能力。对于具有临界电流的断路器,还应增加临界电流开断试验。
  
  在开断能力试验中,断路器的油或气应从断路器专设的排逸孔逸出,不应引起外部闪络。油断路器不允许喷火。开断能力试验完成后,断路器的机械传动部件、非易损件和绝缘瓷瓶不得损坏,实际上应与试验前的状况相同。断路器应能正常操作,其机械特性与试验前相比不应有显著的变化。断路器的主触头不应有严重烧伤,主绝缘不应受到损坏。油断路器的油面应可见。
  
  断路器还应通过开断能力试验检验下列额定参数:①近区故障的额定参数;②额定线路充电开断电流;③额定失步开断电流;④额定电缆充电开断电流;⑤额定单个电容器组开断电流;⑥额定背对背电容器组开断电流;⑦额定感应电动机开断电流;⑧额定空载变压器开断电流;⑨额定电抗器开断电流。
  