1) Thermal power plant auxiliaries
电站给水泵组
2) high-pressure feedwater pump
电站高压给水泵
3) water supply pump station
给水泵站
1.
Unit energy consumption is not suitable for the operation estimate of water supply pump station connected with pressurized pipes directly.
对直接与压力管道相连的给水泵站,运用能源单耗概念进行运营管理评价并不适用。
2.
A project of optimizing and improving water pump capacity was conducted by using improved integer programming in water supply pump stations in a small or medium size town.
采用改进的整数规划法对某中小城镇给水泵站的水泵进行优选和改造 ,实践证明 ,改造后降低了泵站的能耗 ,节约了运行费
4) motor-driven feed-water pump set
电动给水泵组
5) Boiler Feed Pumps
给水泵组
1.
Research on State Trend Prediction of Boiler Feed Pumps Based on LS-SVM;
基于LS-SVM的火电厂给水泵组状态趋势预测研究
6) Water supply pump of electric speed governing
电动调速给水泵组
补充资料:给水泵起停控制
给水泵起停控制
boiler feed-water pump start-up and shutdown control
给水泵起、停控制一般都采用顺序控制系统,其控制对象包括给水泵电动机、辅助油泵、泵出口阀门和再循环阀门。 在停止水泵时,应先将水泵的转速降到最低值后再停止水泵的电动机,这样做的目的是当再次起动水泵时,可以保证电动机在低负载下起动。水泵起动后,需要保持一定流量的给水以冷却泵体,因此,在泵的出口阀门前设有再循环阀门,当泵的流量低于规定值时就要开启再循环阀门,使泵有足够的流t,一般情况下,再循环阀门的动作值是泵最大流量的30%.为了避免在起动时电动机过载,要求水泵在空载条件下起动,也就是当水泵出口母管压力等于零的情况下起动水泵时,应先将泵出口阀门关闭后再起动,而在其他情况下起动水泵时,不论是泵的切换或备用泵自起动,由于水泵出口母管压力已经建立,为了缩短水泵的起动时间以适应尽快带负载的要求,应在泵出口阀门开启情况下起动水泵,而泵的出口逆止阀在泵起动前处于关闭位置,可以保证泵可靠的隔离。在电动机的轴上带有一台主油泵,在电动机运行时.供液力联轴器和各个轴承的润滑用油.在泵起动和停止过程中必须起动辅助油泵。 给水泵顺序控制系统就是按上述运行方式对给水泵起、停全过程进行控制的.控制装里:对于小型给水泵,可采用继电器组件或小型可编程退抖控制器单独构成;而对于大型机组都归入分散拉制系统中的主、辅机顺序控制系统范围内。 对于汽动给水泵,有关其汽轮机的控制可参见给水泵汽轮机控制系统。j .Shu,beng ql ting kongZhl给水泵起停控制(boiler feed一water pumpstart一up and shut一down eontrol)电动给水泵的容量大、压力高、一般配有液力联轴器或变频调速器调速,因此在结构上和运行方式上都有着自己的特点。