1) bus voltage loss
母线电压损失(冶)
2) Circuit Voltage Losing
线路电压损失
4) Voltage loss
电压损失
1.
Simplified calculation of voltage loss of road lamp;
路灯电压损失的简化计算
2.
Relation between line loss rate and voltage loss of power lines
线路的线损率与工程设计中电压损失的关系
3.
Based on a typical example of power network in a coal mining area, the methods of cable selection of main line and branch line, which can meet the voltage loss both on the conditions of normal equipment start and largest and farthest equipment start for ensuring system safety and stable operation were introduced.
本文通过煤矿某采区供电系统的典型示例,介绍在正常和最大最远设备启动时,满足电压损失条件下如何选择干线、支线电缆,以确保系统安全、稳定的运行。
5) busbar voltage
母线电压
1.
In order to address the problems of the alarm setting value of the direct-current equipment in current transformer substations, this paper analyzes the checking charge-discharge results of the batteries and then proposes recommendable values of the direct-current busbar voltage alarming value,so as to offer help to the safe and reliable operation and the maintenance of the direct current system.
通过对目前变电站直流设备报警整定值存在的问题,通过对蓄电池核对性充放电结果的分析,提出了直流母线电压报警值的推荐值,希望对直流系统的安全稳定运行,对直流系统维护提供帮助。
2.
According to the principle of backup power switchover unit of LFP-965, LFP-965 unit can not distinguish two buses without voltage synchronously when public busbar voltage transformer and line voltage transformer are employed at the same time.
根据LFP-965型备用电源自动投入装置的工作原理,分析了在一些电气主接线方式为内桥型接线的变电站中,当母线电压互感器(PT)与线路PT共用时,由于LFP965型备用电源自动投入装置不能判别两段母线是否同时失压,从而限制了其使用范围。
3.
This article introduces an event about protection action causing by the decrease of busbar voltage in Xiaolangdi hydropower station, in order to make people pay attention to voltage management to ensure the safety and stability of power grid and generating units.
对小浪底一起母线电压降低导致保护动作实例进行分析研究,以引起对电压管理的重视,从而确保机组、电网的安全运行。
6) bus voltage
母线电压
1.
We proposed a new method to distinguish the lightning strikes and common short-circuit faults on the basis of the characteristic of the bus voltage signals using S-transform.
基于行波特征区分雷电冲击与短路故障有一定局限性,提出一种利用母线电压信号特征识别雷击与短路故障的新方法。
2.
There are several factors leading to relatively low measured value of bus voltage,so the cause analysis and elimination are necessary.
引起母线电压测量值偏低的原因有多个,必须逐一进行分析排查。
补充资料:电压损失
输配电线路首末两端的电压差值。表示为
ΔU=U1-U2 (千伏)
式中U1、U2分别为线路首末端的线电压,单位为千伏。如用百分值表示,为
式中UN为线路的额定线电压(千伏)。
一般在线路首末端电压的相位差不太大的情况下,可用如下的近似计算公式:式中P为线路所输送的有功功率(兆瓦),Q为线路所输送的无功功率(兆乏),U为线路一端的线电压(千伏),R为线路上的电阻,X为线路的电抗。应用此式时,P、Q、U必须采用同一端的有功功率、无功功率、电压值。
上式表明,线路的电压损失可以分为两部分:一部分是有功功率在线路电阻R上造成的,其表达式为PR/U,另一部分是由无功电流由线路的电抗引起的,为QX/U。110千伏及以上线路,X与R之比约为4~10,所以电抗造成的电压损失占主要部分;电缆线路和低压配电线路上电阻的比重相对地比高压线路大得多,因而电阻R上的电压损失不可忽视。
要减少输电线路,特别是高压输电线路的电压损失,需减小线路的电抗值(如采用分裂导线等措施),而更重要、更经济的方法是减少线路传输的感性无功功率,也就是要尽可能避免无功功率的远距离输送。
ΔU=U1-U2 (千伏)
式中U1、U2分别为线路首末端的线电压,单位为千伏。如用百分值表示,为
式中UN为线路的额定线电压(千伏)。
一般在线路首末端电压的相位差不太大的情况下,可用如下的近似计算公式:式中P为线路所输送的有功功率(兆瓦),Q为线路所输送的无功功率(兆乏),U为线路一端的线电压(千伏),R为线路上的电阻,X为线路的电抗。应用此式时,P、Q、U必须采用同一端的有功功率、无功功率、电压值。
上式表明,线路的电压损失可以分为两部分:一部分是有功功率在线路电阻R上造成的,其表达式为PR/U,另一部分是由无功电流由线路的电抗引起的,为QX/U。110千伏及以上线路,X与R之比约为4~10,所以电抗造成的电压损失占主要部分;电缆线路和低压配电线路上电阻的比重相对地比高压线路大得多,因而电阻R上的电压损失不可忽视。
要减少输电线路,特别是高压输电线路的电压损失,需减小线路的电抗值(如采用分裂导线等措施),而更重要、更经济的方法是减少线路传输的感性无功功率,也就是要尽可能避免无功功率的远距离输送。