1) off-cycle defosting
"中止循环"除霜
2) circulating defrosting
循环除霜
3) reverse-cycle defrosting
逆循环除霜
1.
The dynamic characteristics for both the hot-gas bypass defrosting method and the reverse-cycle defrosting method were compared experimentally on a 55 kW unitary air-to-water heat pump.
在制冷量为55 kW的风冷热泵冷热水机组上,比较了热气旁通除霜和逆循环除霜的性能。
4) reverse cycle defrost
逆循环除霜
1.
The influence of the expansion device on the reverse cycle defrost performance in an air-to-water heat pump was investigated experimentally.
为研究不同节流机构对逆循环除霜时间的影响,分别用一根外径为22mm的旁通铜管和热力膨胀阀作为除霜时的节流机构,在一台名义制冷量为55kW的风冷热泵冷热水机组上进行了实验研究,结果表明:旁通铜管系统与热力膨胀阀系统对比,总的除霜时间减少了40s,其中融霜时间减少了34s,排水时间减少了10s;在恢复阶段,由于制冷剂的流量较大和板式换热器的内容积比较小,两种节流机构的排气压力都剧烈上升,旁通铜管系统上和热力膨胀阀系统分别上升了488 7kPa和389 9kPa;排水阶段结束时,旁通铜管系统的排气压力比热力膨胀阀系统高453 8kPa,并且在恢复阶段排气压力上升的幅度更大,导致旁通铜管系统的排气压力接近高压保护值。
6) prevent things from cycling
终止循环
补充资料:热气除霜冷冻系统
说明:补充资料仅用于学习参考,请勿用于其它任何用途。