1) Coefficient modulation
系数调制
2) modulation index
调制系数
1.
According to modulation index value,the scheme have three modes in whole district: linear modulation mode,overmodulation modeⅠ and overmodulation mode Ⅱ.
该控制策略将整个控制区域按照调制系数的大小分成三种工作模式,线性调制模式、过调制模式Ⅰ和过调制模式Ⅱ。
2.
Two control methods to balance the voltage of capacitors of three--level voltage source inverter by the differentphase--shift angle and by the different modulation index of switching function on positive and negative half wave are proposed.
提出了两种均衡三级电压源逆变器直流侧电容电压控制方法 ,并进行比较 ,认为开关函数正负半波采用不同的移相角的控制方法与采用不同的调制系数的控制方法 ,都可以达到均衡三级电压源逆变器直流侧电容电压的目的 ,且后者更为可靠。
3) modulation factor
调制系数
1.
The research results show that the harmonic distortion of the DSB algorithm is only influenced by the modulation factor,and is not related to either the modulation signal frequency or the carrier signal frequency.
依据一种新型扬声器——声频定向扬声器的基本工作原理,从理论上给出了DSB算法中调制系数对输出信号谐波失真影响的详细推导过程;并指出调制系数越小,失真度越小,但带来的负面效应是小的调制系数将使输出的信号功率相应变小。
4) negative modulation factor
负调制系数
5) modulation factor
调制系数,调制因子
6) phase modulation coefficient
相位调制系数
补充资料:阀门技术注重流量系数和气蚀系数
阀门的流量系数和气蚀系数是阀的重要参数,这在先进工业国家生产的阀门资料中一般均能提供。我国生产的阀门基本上没有这方面资料,因为取得这方面的资料需要做实验才能提出,这是我国和世界先进水平的阀门差距的重要表现之一。
3.1、阀门的流量系数
3.1、阀门的流量系数
阀门的流量系数是衡量阀门流通能力的指标,流量系数值越大,说明流体流过阀门时的压力损失越小。
按KV值计算式
式中:KV—流量系数
Q—体积流量m3/h
ΔP—阀门的压力损失bar
P—流体密度kg/m3
3.2、阀门的气蚀系数
用气蚀系数δ值,来选定用作控制流量时,选择什么样的阀门结构型式。
式中:H1—阀后(出口)压
H2—大气压与其温度相对应的饱和蒸气压力之差m
ΔP—阀门前后的压差m
各种阀门由于构造不同,因此,允许的气蚀系数δ也不同。如图所示。如计算的气蚀系数大于容许气蚀系数,则说明可用,不会发生气蚀。如蝶阀容许气蚀系数为2.5,则:
如δ>2.5,则不会发生气蚀。
当2.5>δ>1.5时,会发生轻微气蚀。
δ<1.5时,产生振动。
δ<0.5的情况继续使用时,则会损伤阀门和下游配管。
阀门的基本特性曲线和操作特性曲线,对阀门在什么时候发生气蚀是看不出来的,更指不出来在那个点上达到操作极限。通过上述计算则一目了然。所以产生气蚀,是因为液体加速流动过程中通过一段渐缩断面时,部分液体气化,产生的气泡随后在阀后开阔断面炸裂,其表现有三:
(1)发生噪声
(2)振动(严重时可造成基础和相关构筑物的破坏,产生疲劳断裂)
(3)对材料的破坏(对阀体和管道产生侵蚀)
再从上述计算中,不难看出产生气蚀和阀后压强H1有极大关系,加大H1显然会使情况改变,改善方法:
a.把阀门安装在管道较低点。
b.在阀门后管道上装孔板增加阻力。
c.阀门出口开放,直接蓄水池,使气泡炸裂的空间增大,气蚀减小。
综合上述四个方面的分析、探讨,归纳起来对闸阀、蝶阀主要特点和参数列表便于选用。两个重要参数在阀门运用中 。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条