Aimed at the short circuit current of 35kV bus is too large,it impacts the steady operation,some measurements are taken to restrict short circuit current,such as installing current-limit reactor on the preliminary equipment,mirocomputer differential bus protection on the secondary protection or adding a time-delay quick-break protection on the side of upper transformer.
针对35kV母线短路电流过大,影响母线安全运行的情况,在一次设备上采取加装限流电抗器的办法来限制母线短路电流,在二次保护上加装微机母差保护或在上级变压器35kV侧新增一段限时速断保护以较短时间切除母线故障。
4) bus differential protection
母线差动保护
1.
The principle of REB103 bus differential protection for the Three Gorges Left Bank Hydropower Station is introduced in detail.
详细叙述了三峡左岸电站REB103型母线差动保护装置的测量原理,针对投产初期保护装置存在的缺陷进行了分析,提出了改进意见,并得到了实施。
2.
The Characteristic of middle impedance relay was elaborated, as an example of bus differential protection of RADSS type.
以RADSS型母线差动保护为例,阐述了中阻抗型差动继电器的原理特点。
3.
This paper simply describes the mathematic model for computer setting calculation of bus aifferential protection,consideration of operation mode,protection setting principle,and setting calculation Program of the bus differential protection written basing on the above method.
本文简要地介绍了母线差动保护计算机整定计算的数学模型,运行方式的考虑,保护整定原则,以及基于上述方法编制的母线差动保护整定计算程序,该程序已在实际电网中应用,满足工程计算要求
5) pole bus differential protection
极母线差动保护
1.
3GS) HVDC interconnection project and give the advice for the future HVDC projects, we analyzed a fault trip of pole bus differential protection during the system debugging of Yidu-Huaxing 3GS HVDC that connects Central China Power Grid with East China Power Grid.
为确保三上工程的顺利投运,以及为后续高压直流输电工程设计提供建议,分析了宜都—华新系统调试期间一次极母线差动保护误动作的情况,提出不平衡电流是本次误动作的主要原因。
6) microcomputer-based bus protection
微机母线保护
1.
This scientific paper make a brief introduction about the judgement and treatment of microcomputer-based bus protection if the disconnecting switches have some wrong with auxiliary contacts when the busbar operation vary.
简要介绍微机母线保护在母线运行方式变化时,容易出现的辅助触点出错判断及处理方法,并分析了双母线分列运行时保护装置灵敏度和可靠性自适应问题。
2.
The development of microcomputer-based bus protection is reviewed.
介绍了微机母线保护的发展过程,举例阐述了西门子7SS60集中式及7SS52分布式微机母线保护系统的保护原理,以及电流互感器饱和判据、结构及功能,并做了大量分析、论证及比较,指出现阶段集中式母线保护装置仍然是母线保护发展的主流,分布式母线保护系统更能适应综合自动化的要求,是将来发展的必然趋势。
补充资料:变压器差动保护系统调试
变压器差动保护系统调试
commissioning of the differ- ential protection system for transformer
b ianyaqi chadong baohu xitong tiaoshi变压器睡动保护系统调试(eommissioningof the differential Proteetion system for trans-former)对流入变压器和自变压器流出的两侧电流,经电流互感器检测变换之后进行比较,其电流差值反映出变压器的内部故障情况.根据这一原理,由电流互感器、差动继电器、断路器跳闸机构组成的保护系统称为变压器差动保护系统.当电流互感器的变比和结线方式与被保护的变压器相适应时,变压器正常运行电流及变压器以外的穿越性故障电流不会使差动保护动作.空载变压器接入电源时,电源侧向变压器流入较大的励磁涌流,为减少它对保护系统的影响,消除误动作,变压器差动保护系统中设有速饱和变流器或谐波制动电路。变压器差动保护系统的调试分差动保护继电器的单体调试和差动保护系统模拟试验两个步骤. 差动保护继电器的单体调试变压器差动保护继电器依其结构特点可分为机电型、整流型、静态型等。机电型差动保护继电器由速饱和变流器、电磁动作的执行继电器、换档擂接板等组成,其调试项目主要有:(1)外观检查,插接与机械动作部分的检查和调整。(2)电磁式执行继电器的常规调试。(3)速饱和变流器的特性试验:检查各绕组极性与结线的正确性;测定变流器伏安特性曲线;通入试验电流,测定执行继电器动作时各绕组分档的动作电流安匝数,并将其整定到设计规定的范围内;测定直流助磁特性,即测定相对动作电流。=(‘/i。)和偏移系数K(1/1)间的函数关系。式中,I为速饱和变流器一次侧通入的直流试验电流(A)八为通入直流分量I时速饱和变流器一次侧的交流动作电流(A);i。为未通直流分量时的交流动作电流(A)。(4)在整定位置下测定保护继电器的整组伏安特性,即差动继电器输入差动电流信号安匝数与执行继电器线圈端电压之间的关系,以判别差动继电器工作磁通密度选取是否合适。 整流型差动保护继电器由差动元件和瞬动元件两部分组成。差动元件包括工作回路、比率制动回路、谐波制动回路及直流比较回路。调试项目主要有:(l)工作回路最小动作电流与返回电流的测定,动作电流整定。(2)比率制动回路动作特性试验。给工作回路和制动回路同时通入试验电流,测定继电器产生输出动作时两试验电流数,绘制出它们的函数关系曲线(即比率动作特性曲线),按照保护设计要求对比率动作特性进行整定。在无特殊要求时,两试验电流取同相位电流。