1) Impulse ground impedance
冲击接地阻抗
1.
There are a lot of damage by lightning on transmission line towers, but now ground impedance measurement only can measure industry frequency ground impedance, but rarely measure impulse ground impedance, so it is very necessary to research a new method of measuring tower impulse gr.
输电线路杆塔受雷击引起的事故较多,但目前杆塔接地阻抗的测量一般只注重工频接地阻抗的测量,而很少能测量接地装置的冲击接地阻抗,因此研究一种测量杆塔冲击接地阻抗的测量方法非常有必要。
2) impulse grounding resistance
冲击接地电阻
1.
Considering some factors,including the different operation mode and lightning strike location,also calculates and analyzes the infection of the impulse grounding resistance of transmission tower,the lightning arresters arranging and parameter for protection effect.
采用PSCAD/EMTDC程序计算分析了西北电网兰州东-银川东输变电工程750kV银川东变电站330kV线路雷电侵入波过电压保护,考虑了不同运行方式、不同雷击点的情况,还计算分析了杆塔冲击接地电阻、避雷器的布置及参数对保护效果的影响。
2.
It is pointed out that the impulse grounding resistance is an important factor for the safety of power system,and a new method of measuring grounding resistance is proposed.
指出了电力系统接地网中冲击接地电阻对电力系统接地安全的重要影响,并提出了一种接地测量的新方法。
3.
A portable test method for impulse grounding resistance is proposed,on base of analyzing the existing calculation and measurement of tower impulse grounding resistance.
在总结现有的杆塔冲击接地电阻的计算测量方法的基础上,研制了便携式杆塔冲击接地电阻测量系统。
3) impulse impedance
冲击阻抗
4) self-surge impedance
自冲击阻抗
5) ground impedance
接地阻抗
1.
This paper presents a PC based instrument for ground impedance measurement.
描述了一种计算机辅助测量接地阻抗的设备,该设备引入了测量接地点与辅助接地点之间的瞬时电流,通过测量被测接地点的接地电势差,利用校正的方法消除外部噪声的影响,再用估测的方法,测得接地电势的升高值和接地阻抗值,从而克服了传统的电压测量法的种种弊端。
2.
Application of PC based instrument for ground impedance measurement can overcome the shortcomings in traditional voltage drop measurements.
采用计算机辅助接地阻抗测量设备 ,可以克服传统的电压降测量法的种种弊端。
6) grounding impedance
接地阻抗
1.
Analysis of inductive component influence factors of grounding impedance of substation grounding grid
变电站地网接地阻抗感性分量影响因素分析
2.
Connecting with exterior grounding conductor is an effective measure to decrease ground grid grounding impedance.
引外接地是一种降低地网接地阻抗的有效措施。
3.
This paper makes a study on principles of grounding impedance measurement and derives the formula for calculating grounding impedance.
对接地阻抗测量原理进行研究,分析推导出接地阻抗计算公式。
补充资料:接地
接地 grounding 为保证电工设备正常工作和人身安全而采取的一种用电安全措施。接地通过接地装置来实现。接地装置将电工设备和其他生产设备上可能产生的工作电流、漏电流、静电荷以及雷电流等引入地下,从而避免人身触电和可能发生的火灾、爆炸以及电磁干扰等。 接地的种类有工作接地、保护接地、防雷接地和屏蔽接地等。①工作接地。变压器、发电机的中性点接地,用以保证电力系统在正常和故障情况下具有适当的运行条件和继电保护、自动装置的正常工作。②保护接地。把电工设备的金属外壳接地,以防止绝缘损坏时金属外壳上存在电压危及与之相接触的人员。③防雷接地。用来泄放避雷器的雷电流 ,降低其上的电位,从而保证电工设备和人身安全,防止火灾和爆炸事故。④屏蔽接地。用来消除静电场、电磁场对人体的危害并防止电磁场对通信和信号的干扰。为达到上述目的,接地装置需有一定的散流能力,即需保证其接地电阻不超过一定的数值。接地装置上的工频交流或直流电压与通过它流入大地的电流之比称为接地电阻。散泄雷电冲击电流时的冲击接地电阻是指电压峰值与电流峰值之比。接地电阻主要是电流在地下流散途径中土壤的电阻,接地体本身的电阻和接地体与土壤接触的电阻小得可以忽略。 接地装置由接地体和接地线组成。直接与土壤接触的金属导体称为接地体。电工设备与接地体连接的金属导体称为接地线。接地体分为人工接地体和自然接地体。人工接地体可用垂直埋置的长2~3米、外径为35~50毫米的钢管,或用40毫米×40毫米×4毫米角钢;水平接地体可用直径8~10毫米圆钢,或30毫米×4毫米、40毫米×4毫米扁钢。人工接地体的顶端应埋入地表面下0.5~1.5米。自然接地体可用自来水管或建筑物钢筋混凝土基础等。 |
说明:补充资料仅用于学习参考,请勿用于其它任何用途。