说明:双击或选中下面任意单词,将显示该词的音标、读音、翻译等;选中中文或多个词,将显示翻译。
您的位置:首页 -> 词典 -> 干式空芯限流电抗器
1)  dry-type air-core current-limited reactor
干式空芯限流电抗器
2)  dry type air cored reactor
干式空芯电抗器
1.
On the basis of comparison of three methods analytic method,numerical method and mixed method,the detailed analysis and calculation of the eddy losses of the dry type air cored reactor is provided using the mixed calculating method.
在比较解析法、数值计算法和混合计算法三种方法的基础上,采用混合计算法,对干式空芯电抗器的涡流损耗进行了较为详细的分析和计算。
3)  dry type semi-core reactor
干式半芯电抗器
1.
A dry type semi-core reactor burnout accident during operation was analyzed and the corresponding modification proposal and measures were put forward.
对一起干式半芯电抗器在运行中烧毁事故进行了详细分析,并提出了相应的改进建议和措施。
4)  air-core dry-type reactor
空心干式电抗器
5)  dry hollow reactor
干式空心电抗器
1.
Dry hollow reactor is an inductive device of the electrical power system, which has important roles in many respects such as current limiter, regulator, reactive compensation, and so on Dry Hollow Reactor is one of the new type reactors which was developed in recent years.
干式空心电抗器是在电力系统中用于限流、稳压和无功补偿等方面的一种电感装置。
6)  dry-type air-core reactor
干式空心电抗器
1.
Development and application of design software of dry-type air-core reactor;
干式空心电抗器设计软件开发与应用
2.
Analysis on tree discharge on the surface of dry-type air-core reactors is made through a series of characteristic tests on breakdown of epoxy resin compound insulation, surface discharge test on reactor model, electric field calculation Of insulation structure and study on monitoring and prevention of surface discharge on reactors.
针对户外干式空心电抗器表面树枝状放电现象,进行包封绝缘材料电击穿特性试验、电抗器模型表面放电试验、绝缘结构电场数值计算、电抗器表面放电检测与防护的试验研究。
3.
With the parameters of a real dry-type air-core reactor, the emulation analysis verifies that the impulse-voltage method is suitable to test its turn-to-turn insulation.
基于脉冲电压法原理,对一个实际干式空心电抗器的电路参数进行了计算机仿真分析,验证了脉冲电压法对干式空心电抗器进行区间绝缘检测是可行的。
补充资料:限流电抗器


限流电抗器
current-limiting reactor

x 10nl一u drankongql限流电抗器(eurrent一limiting reactor)与翰电线路申联用以限制电力系统短路电流的电扰器,又称串联电抗器。通常安装在线路出线段或母线段之图1限流电抗器接线图间(见图1)。当线路或母线发生故障时,限流电抗器能使后接设备的短路电流不超过容许值,并使母线电压保持在额定电压的60%~70%之间。带有中心抽头和两个对称份的电抗器称为分裂电抗器,使用时中心抽头接电源,两份接负荷(见图z)。在多台变压器和多回线路的史电所,限流电抗器还可用来进行阻抗匹配,使变电所达到最佳运行状态。 限流电抗器在额定电流下的电压降,通常为额定电压的3%~10%。分裂电抗器两个臂的电抗值和载流量相同,正常工作时两臂的电流方向相反,大部分磁通相互抵消,从而图2分裂电抗器接线图其电压降减小,当一有发生故障时,磁通不能抵消,电抗值增大,从而起到限流作用。 额定电压在35 kV以下、额定电流为200~3000A的户内式限流电抗器,通常为空芯混凝土柱式结构。额定电压在35kV及以上的限流电抗器,一般为空芯油浸户外式结构,油箱内壁加装磁分路或磁屏蔽.近年来又研制成一种新型玻瑞纤维结构的空芯式电抗器,其造型简单轻巧,适应于户内和户外。 限流电抗器通常都做成单相式,组成三相时有三相垂直重登、两相垂直重亚一相并列、三相并列等三种排列方式(见图3)。排列方式不同,其绕组的绕制方向和匝数要求也不同。由于限流电抗器的磁通在空气中形成回路,所以安装时与屋顶、四壁和地面需要保持一定的距离。骤篡,赢图3电抗器三相排列方式(a)三相垂宜t登;(b)两相垂1t登,一相并列;(c)三相并列
说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条