1) D23 differential bus protection
D23母差保护
2) busbar differential protection
母差保护
1.
Reason analysis and preventive measures of a busbar differential protection maloperation
一起母差保护误动原因分析及防范措施
2.
Combining the actual application of BP-2A,P-2B and RCS915A/B busbar differential protection devices manufactured by NanRui Company,the problems needing attention of microcomputer-based busbar differential protection in the operating maintenance are introduced.
结合南瑞公司生产的BP-2A、BP-2B型及RCS915A/B型母差保护装置在实际中的应用情况,介绍了微机型母差保护在运行维护中应注意的问题,并对运行中微机母差保护的误动进行分析,确保加入电网的微机型母差保护装置安全稳定运行,使其更好地为电网服务。
3) bus differential protection
母差保护
1.
Discussion on substation bus differential protection retrofitting;
变电站母差保护技术改造方案探讨
2.
Consummative running of duplicate-busbar segmentation and bus differential protection in substation;
变电站双母线分段与母差保护完善运行
3.
This paper analyzed the problems in RADSS bus differential protection when bus gang switch operates as by-pass switch in combination with the handling process of abnormal primary equipments,and presented the improving measures.
结合一次设备异常处理过程分析了在母线兼旁路开关带路运行方式下RADSS型母差保护存在的问题及改进措施。
4) busbar protection
母差保护
1.
Analysis of dangerous points of the operation of busbar protection in local systems;
地区电网母差保护调度运行危险点分析
2.
Analysis on maloperation causes of busbar protection in Daqing Oil Field Thermal Power Plant;
大庆油田热电厂母差保护误动原因分析
3.
REB103 is a mid-impedance differential relay for busbar protection.
通过对ABB公司中阻抗母差REB103在出线故障时误动和事故后详细试验情况分析,提出了REB103母差保护的改进方案,有助于提高该母差保护在特定工况下的运行稳定性,可有效地提高电网的安全运行水平。
5) differential busbar protection
母差保护
1.
The problem discussion of differential busbar protection and incoming line standby automatic protective system in 110 kV substation;
110kV变电站110kV母差保护与进线备自投有关问题探讨
6) bus protection
母差保护
1.
Experience in putting BP-2B digital bus protection into operation at worksite in running state
BP-2B型微机母差保护现场改造经验
2.
220 kV WMZ-41A bus protection anomaly analysis and preventive measures in the Chengtou substation
城头变220kV WMZ-41A母差保护异常现象的分析及预防措施
3.
Two reasons of causing transformer to be saturated and then affecting distributed bus protection are analysized.
通过试验实测参数对闭合磁路电流互感器暂态特性进行了研究,分析了引起互感器饱和从而影响分布式母差保护工作的两个原因:一是非周期分量引起故障电流的大幅度偏移;二是缓慢衰减的直流分量引起故障电流的大幅度偏移。
补充资料:变压器差动保护系统调试
变压器差动保护系统调试
commissioning of the differ- ential protection system for transformer
b ianyaqi chadong baohu xitong tiaoshi变压器睡动保护系统调试(eommissioningof the differential Proteetion system for trans-former)对流入变压器和自变压器流出的两侧电流,经电流互感器检测变换之后进行比较,其电流差值反映出变压器的内部故障情况.根据这一原理,由电流互感器、差动继电器、断路器跳闸机构组成的保护系统称为变压器差动保护系统.当电流互感器的变比和结线方式与被保护的变压器相适应时,变压器正常运行电流及变压器以外的穿越性故障电流不会使差动保护动作.空载变压器接入电源时,电源侧向变压器流入较大的励磁涌流,为减少它对保护系统的影响,消除误动作,变压器差动保护系统中设有速饱和变流器或谐波制动电路。变压器差动保护系统的调试分差动保护继电器的单体调试和差动保护系统模拟试验两个步骤. 差动保护继电器的单体调试变压器差动保护继电器依其结构特点可分为机电型、整流型、静态型等。机电型差动保护继电器由速饱和变流器、电磁动作的执行继电器、换档擂接板等组成,其调试项目主要有:(1)外观检查,插接与机械动作部分的检查和调整。(2)电磁式执行继电器的常规调试。(3)速饱和变流器的特性试验:检查各绕组极性与结线的正确性;测定变流器伏安特性曲线;通入试验电流,测定执行继电器动作时各绕组分档的动作电流安匝数,并将其整定到设计规定的范围内;测定直流助磁特性,即测定相对动作电流。=(‘/i。)和偏移系数K(1/1)间的函数关系。式中,I为速饱和变流器一次侧通入的直流试验电流(A)八为通入直流分量I时速饱和变流器一次侧的交流动作电流(A);i。为未通直流分量时的交流动作电流(A)。(4)在整定位置下测定保护继电器的整组伏安特性,即差动继电器输入差动电流信号安匝数与执行继电器线圈端电压之间的关系,以判别差动继电器工作磁通密度选取是否合适。 整流型差动保护继电器由差动元件和瞬动元件两部分组成。差动元件包括工作回路、比率制动回路、谐波制动回路及直流比较回路。调试项目主要有:(l)工作回路最小动作电流与返回电流的测定,动作电流整定。(2)比率制动回路动作特性试验。给工作回路和制动回路同时通入试验电流,测定继电器产生输出动作时两试验电流数,绘制出它们的函数关系曲线(即比率动作特性曲线),按照保护设计要求对比率动作特性进行整定。在无特殊要求时,两试验电流取同相位电流。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条