说明:双击或选中下面任意单词,将显示该词的音标、读音、翻译等;选中中文或多个词,将显示翻译。
您的位置:首页 -> 词典 -> 动导数试验
1)  dynamic derivative model test
动导数试验
2)  vibration test parameter
振动试验参数
3)  numerical virbration experiment
数模振动试验
4)  pilot test
先导试验
1.
Results and dynamic characteristics of pilot test of surfactant/polymer binary combination flooding in western No. 7 district in Gudong Oilfield;
孤东油田七区西南二元复合驱油先导试验效果及动态特点
2.
Composite sand control pilot test in Shu 3 area;
曙三区综合防砂先导试验研究
3.
Optimization of succeeding water flooding plan after steam drive pilot test in Block Qi40;
齐40块蒸汽驱先导试验后续水驱方式优选
5)  Missile test
导弹试验
1.
In accordance with existing some hard problems in the use of sequential and sequential truncated inspection and brought the definite error to the test,optimization design of sequential and sequential truncated inspection scheme for missile test is carried out by using the method of Monte Carlo random simulation and the idea of modern optimization,and the result is satisfactory.
针对序贯检验和序贯截尾检验方法在工程实际应用中存在的一些难以解决的问题 ,且给试验带来一定的误差 ,采用蒙特卡洛随机模拟方法和现代优化设计思想 ,对战术导弹试验中的序贯检验和序贯截尾检验方案进行优化设计 ,取得了较好的效果 。
6)  test guidance
试验导则
1.
This paper introduced the new IEC60076 -4 test guidance of lightning surge and switching surge for power transformer and reactor, which is the new edition of IEC722 (1982).
介绍了新的IEC60076—4电力变压器和电抗器雷电冲击和操作冲击试验导则,它是IEC722(1982)的新版,比原导则增加与完善了新的内容。
补充资料:动/热稳定试验
      检验开关的主回路和接地回路(在适用的地方)承载短路电流能力的试验。其中,动稳定试验又称峰值耐受电流试验,热稳定试验又称短时耐受电流试验。
  
  机械式开关在闭合位置所能耐受短路电流的能力可用额定峰值耐受电流或额定动稳定电流Ir(短路电流第一个大半波的电流峰值)、额定短时耐受电流或额定热稳定电流 I(有效值)以及额定短路持续时间或额定热稳定时间t3个参数来表示。
  
  动/热稳定试验可在任意温度、任意适当电压下进行,频率应为受试产品的额定频率,其偏差为±10%。
  
  动/热稳定试验通常联合进行,如因试验设备限制也可以分开进行。试验时,其I2t和动稳定电流峰值Ir不得低于规定值。且与规定值的差为:I2t不得超过10%;Ir值不得超过5%。
  
  试品在承受动稳定电流和热稳定电流的作用后,不得有下列情况之一,否则试品的动/热稳定性能为不合格:①影响试品正常工作的任何机械损伤和局部绝缘损伤而引起的绝缘性能降低;②试品出现自动分闸及各种联锁失灵等;③触头出现熔焊或有影响工作的烧伤;④配人力操动机构的试品用人力合分各3次,配电动操动机构的产品用规定的最低电(气、液)压合分各 3次中出现拒分、拒合;⑤试品的机械特性超过技术条件规定范围。
  