1) generator transformer
发电机变压器
1.
In view of the design for Manwan Hydropower Station, the fundamental disposition, features of protectors and the design concept of generator transformer are stated as follows.
本文介绍了漫湾水电站发电机变压器保护的基本配置情况、保护装置特点和设计中的一些设想,并通过近三年的运行实践,总结了该套保护存在的一些问题及解决方法。
2) generator-transformer unit
发电机-变压器组
1.
Some opinions about setting differential protection for large generator-transformer units;
关于大型发电机-变压器组差动保护整定计算的几点见解
2.
Development of an integrative state detection and record system for generator-transformer unit;
新型发电机-变压器组微机监录与分析系统的研究
3.
The generator-transformer unit protective system in Shajiao C Power Station is equipped with dual generator differential protections and dual main transformer differential protections,with the generator impedance protection and the main transformer impedance protection respectively functioning as backup protection for the generator and the main transformer.
沙角C电厂发电机-变压器组保护装置配置两套发电机差动保护、两套主变压器差动保护,用发电机阻抗保护、主变压器阻抗保护分别作为发电机和主变压器的后备保护。
3) generator-transformer unit
发电机变压器组
1.
The current application situation of China-made digital fault recorders for generator-transformer units is presented.
主要分析国产发电机变压器组故障录波器应用现状。
2.
The generator-transformer units were also reconstructed so as to raise the capacity of the units to 220 MW.
为适应国产三缸三排汽200 MW汽轮发电机组全面技术改造的需要, 广东省沙角A电厂分别于2000年和2002年对一期3台200 MW机组中的2号和3号汽轮机进行了三缸通流改造, 同时对原发电机变压器组也进行了改造, 使机组增容至220 MW。
3.
The reformation and operating situation of relay protection device of generator-transformer unit of Geheyan hydropower plant are introduced, and the practical peculiarities of DRS-COMPACT digital relay made by Elin Company are described.
介绍了隔河岩电厂发电机变压器组继电保护的改造及运行情
4) generator-transformer set
发电机变压器组
1.
Research on COM+ based fault recording analysis system software for generator-transformer set;
基于COM+技术的发电机变压器组故障录波分析系统软件
5) generator transformer unit
发电机变压器组
1.
This article introduces the new principles of digital proctection for generator transformer unit,including deviation of power frequency (DPFC) percentage differential relay, variable slope percentage differential relay, asynchronous method of TA saturation recognition, current percentage restricted stator inter-turn relay, etc.
介绍了大型发电机变压器组装置的几项保护新原理,包括发电机工频变化量比率差动、变斜率比率差动、异步法TA饱和判别、电流比率制动匝间保护等。
2.
The generator transformer unit protection in Hengyun C Power Plant is defective in fundamental design, logical circuit and external interface, which would inconvenience the actual operation and cause maloperation of the protection.
恒运C电厂发电机变压器组 (以下简称“发变组”)保护在原理设计和逻辑回路上均存在缺陷 ,与外部的接口也存在问题 ,使运行操作不便 ,也容易造成保护误动作。
6) generator-transformer units
发电机变压器组
1.
This paper introduces the specialties of WFBZ-01 microprocessor-based protective relays, which is used in the large generator-transformer units in Hebei power stations.
文章介绍了在河北省开始使用的WFBZ - 0 1微机型发电机变压器组保护装置的软硬件特点 ,结合现场的调试和运行情况 ,对装置的主要保护功能和一些技术问题进行了讨论与分析。
补充资料:发电机-变压器组接线
发电机-变压器组接线
generator transformer block scheme
发电机一变压器联合单元接线两组或两组以上单元接线在高压侧的联合,见图(c)。优点是:①机组与主变压器台数相同,但节省了高压断路器,并减少了主变压器至开关站的进线回路数,有利于进线布!和简化高压侧接线。②与单元接线比较,机组停机可较方便地由主变压器倒送厂用电源。③与扩大单元接线比较,不致因主变压器故障或检修而较长时间地影响本单元全部机组容量送出。缺点是:①主变压器高压侧有并联母线和隔离开关,增加变压器场地布置面积。并联母线或高压断路器故障,影响本单元全部机组容量送出。②任一台主变压器故障或检修,接在本单元的全部机组需短时停机。③一台机组停机可断开发电机电压断路器,但主变压器仍带电,增加空载损耗。昌昌昌昌岛昌昌 发电机变压器组接线方式简图 (a)单元接线;(b)扩大单元接线;(c)联合单元接线 这种接线适用于机组台数较多的大型电站,也适用于变压器场地布置条件允许,但电站为分期建设且过渡时间较长,因而采用联合单元接线较扩大单元接线有利的场合。另外,由于设备制造或运拾条件限制等原因,采用扩大单元接线需用单相变压器或组合式三相变压器,而联合单元接线可用普通型三相变压器,通过技术经济比较证明有利时也可采用。fod旧nJ一b旧nyoq一zu Jlex旧n发电机一变压器组接线(generator trans-former block seheme)发电机和变压器申联连接的电路。常用的接线方式有单元接线、扩大单元接线以及联合单元接线。 发电机一变压器单元接线1台机组接1台主变压器(双绕组或三绕组或自藕变压器),见图(a)。优点是:①发电机与主变压器容量协同,接线简单清晰,元件故障影响范围小,运行可靠,操作方便。②发电机电压设备元件少,布置简单,维护工作量小。③继电保护简单。缺点是:①主变压器和高压断路器数量较扩大单元接线多,增加布置场地和设备投资。②主变压器故障时影响机组送电。 这种接线一般适用于单机容量在100 Mw及以上的大容量机组。当单机容量小于100 MW,如机组台数较少,或经方案比较,采用其他接线方式不合适时,也可采用。 发电机一变压器扩大单元接线两台或两台以上机组接l台主变压器,见图(b)。优点是:①接线简单清晰,运行维护方便。②主变压器台数及其相应的高压开关设备比单元接线少,有利于简化高压侧接线,可缩小布置场地和节约投资。③任一台机组停电,不影响接在主变压器低压侧的厂用电源供电,即使本单元全部机组停机,仍可继续由电力系统经主变压器倒送,提高了厂用电供电的可靠性。缺点是:①主变压器故障或检修时,两台或两台以上机组容量不能送出。②增加发电机电压断路器和增大发电机电压侧短路容量。为限制短路容量,变压器低压侧可用分裂绕组变压器,但其价格较普通型变压器贵。 这种接线适用范围较广,大、中、小型电站均有采用。扩大单元的主变压器容量要与电力系统的总容量和备用容1相适应,一般不大于系统总装机容量的8%~10%,并要满足主变压器故障时系统稳定运行的要求。另外,当水电站仅有一个扩大单元时,要注意避免在变压器回路故障或检修时造成大量弃水和影响下游供水等。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。