1) the capability of the leading phase of generator
发电机进相运行能力
2) generator leading running
发电机进相运行
1.
The necessity, feasibility and reliability of generator leading running are justified first with actual measurements and then through theoretical analysis, and it is concluded that generator leading running can ensure safe and efficient operation of generators.
发电机进相运行是一种调整电网无功功率降低电网电压的切实可行手段。
4) phasing operation of turbo-generator
汽轮发电机调相运行
5) generator operating under excitation
发电机进相
1.
The feasibility that the system voltage could be adjusted when generator operating under excitation is demonstrated.
针对此情况,通过计算、分析、试验等方法对重庆电网进行无功优化研究,提出几种方案,综合比较分析最终选取发电机进相为解决方案,并通过试验论证了发电机进相运行调控系统电压的可行性,通过对重庆电厂发电机的进相运行,使重庆220kV电网低谷电压控制在232kV以下,改善了重庆电网运行性能,加强了系统协调稳定,取得了一定的经济效益。
补充资料:水轮发电机组进相运行
水轮发电机组进相运行
leading power factor operation of water turbine generator set
shu一}unfodlonJ一zul}nxlong yunx一ng水轮发电机组进相运行(leading power faetoroperation of water turbine generator set)水轮发电机组处于欠励运行,以吸取电力系统刹余的容性无功功率又送出有功功率的一种运行方式。对于长距离送电的超高压、特高压线路,在轻负荷时,由于刹余容性无功功率,引起送电端电压上升,接近或超过电力系统运行电压的上限,严重地影响电力系统电压质量与安全运行。为降低此电压,可以采用并联电抗器来吸收电力系统剩余的容性无功功率,虽也能达到降低电压的目的,但设备投资较大,不如水轮发电机组进相运行简单、安全、经济、方便。 水轮发电机组进相运行后,可以降低送端电压,节约电能,改善电网的供电质量,保证用户设备安全,提高电站经济效益.这是由于定子电压下降,转子电流下降,使水轮发电机的铁损也随之下降,转子铜损也降低,虽然此时定子铜损也相应增大,但综合的结果,发电机总损耗还是下降的,节能效果是明显的. 水轮发电机组进相运行能力的大小,受其静态稳定极限、定子铁芯、定子端部金属结构件的温升和定子过电流的限制。更主要的是受电厂厂用母线电压限制。因此,按中国水利电力部1982年颁布的《发电机运行规程》规定:“发电机是否能进相运行,应遵守制造厂的规定,制造厂无规定时,应通过试验来确定”。 水轮发电机组进相运行时,其励磁装t最好带电力系统稳定功能,或独立装设电力系统稳定装t(PSS),这样可以提高静态稳定能力,即使在功角达到或超过90。时,机组仍能稳定运行,并且励磁电流的调节也很平稳。因此,水轮发电机组在电力系统负荷低谷时,采用进相运行,可改善电力系统电压质t。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条