The results of the research on contamination flashover performance of DC insulator strings for ±500 kV HVDC system are presented and the ±600 kV artificial pollution test equipment for DC contamination in China Electric Power Research Institute(CEPRI)is described.
介绍了用于±500kV高压直流输电系统的直流绝缘子串污秽闪络特性的研究结果和中国电力科学研究院±600kV直流污秽试验装置,进行了与国外2个实验室的比对试验,验证了污秽耐受电压与绝缘子串长的线性关系,对污秽均匀分布和不均匀分布情况下的长串悬式绝缘子的污秽闪络电压特性进行了试验研究,得到了大量有价值的试验数据。
3) Adhesive characters
附着特性
4) pollution performance
污秽性能
1.
The anti-seismic performance of lightning arrester was also calculated and analyzed with finite element method, and according to IEC60099-4 standard, the pollution performance for lightning arrester was tes.
其中,对避雷器的电位分布采用有限元法进行了计算,对其加装并联电容前后的电位分布也进行了分析比较;对避雷器的抗震性能采用有限元法进行计算和分析;并按IEC600994标准规定对避雷器的污秽性能进行了试验验证。
5) withstand performance of artificially polluted insulator
人工污秽耐受特性
6) dirt collection resistance
耐污垢附着性
补充资料:污秽表面放电
污秽表面放电 pollution surface discharge 介质表面沾染污秽时所引起的沿面放电。简称污闪。固体介质表面沾染污秽又同时变潮后,污秽层中所含的可溶性盐类和酸、碱等溶于水膜,形成离子电导,使污秽表面通过较大泄漏电流;沿面闪络电压显著降低,严重时能降低到清洁表面闪络电压的10%以下。雾、露、细雨和溶雪天气时,绝缘子甚至会在工作电压下闪络,严重影响电力系统的安全运行。因此,污闪已成为高压和超高压电工设备选择外绝缘水平的主要依据。防止污闪和提高污闪电压的措施有:①定期清扫和用水冲洗绝缘子和绝缘套管。②改进绝缘子结构使刮风、下雨时能自行清扫。③增大泄漏距离,选取合理的泄漏比矩(每千伏工作线电压需要的泄漏距离)。④给绝缘表面上半导体釉或涂硅油等憎水材料。⑤尽量使高压输电线路避开污秽区,避免在污秽区建高压变电所。
|