1) SF6 gas insulated substation (GIS)
SF6气体绝缘变电站
2) gas insulated substation(GIS)
气体绝缘变电站
1.
It is known that switching operation in gas insulated substation(GIS) is an important source of electromagnetic disturbances.
作为气体绝缘变电站(GIS)常规操作之一的隔离开关操作是变电站内重要的电磁干扰源,其产生的暂态电磁波有可能在二次电缆中感应出危险的电压并进入GIS的控制设备和保护设备,影响它们的正常运行。
2.
With the widespread application of gas insulated substation(GIS),due to its numerous merits,such as large miniaturizing effects,good anti-contamination characteristics,easy maintenance and good environmental adaptability.
随着超高压气体绝缘变电站(GIS)的广泛使用,由隔离开关(DS)和断路器(CB)操作引起的快速暂态过电压(VFTO)引发的绝缘事故也越来越多。
3) GIS
气体绝缘变电站
1.
Due to the turning on or off operation of the circuit breakers and the disconnected switches, strong electromagnetic interference in gas-insulated substations (GIS) is common.
气体绝缘变电站(GIS)在开关操作厂会产生秀强的瞬态波过程,可通过外壳向外界辐射电磁场,对变电站二次设备的正常运行产生严重干扰。
2.
The application of gas insulated substation(GIS) has expended year by year, Harm of the very fast transient voltages (VFTO) caused during disconnecting switches (DS) operation becomes more obvious.
随着超高压气体绝缘变电站(GIS)的广泛使用,由隔离开关(DS)操作引起的快速暂态过电压(VFTO)的危害更加明显。
3.
We analytically studied the characteristics of VFTO produced in gas-insulated substation (GIS) during disconnector (DS) operation and traveling along GIS bus from the gas-insulated switchgear to the terminal of the transformer.
为此从理论上分析了SF6气体绝缘变电站(GIS)中的VFTO从开关到变压器线端的传输特性。
4) gas insulated substation (GIS)
气体绝缘变电站
1.
A new method is proposed to calculate transient radiation field from the metallic enclosure of gas insulated substation (GIS).
提出了一种计算气体绝缘变电站(GIS)金属外壳暂态辐射场的新方法:首先运用矢量匹配法对用NEC计算的频域格林函数进行拟合,拟合结果在时域内表示为指数函数和的形式;然后利用递归卷积在时域内直接计算实际输入下的辐射场。
5) Gas insulated substation
气体绝缘变电站
1.
Research on the Electromagnetic Interference Due to Switching Operation in Gas Insulated Substation;
气体绝缘变电站开关操作产生的电磁干扰问题研究
2.
The Study on Transformer in Gas Insulated Substation Influenced by Very Fast Transient Overvoltage;
特快速暂态过电压对气体绝缘变电站变压器影响的研究
3.
With the development of power industry and the rise of voltage class, more and more gas insulated substations (GIS) are used in modern power systems.
随着我国电力工业的高速发展和电压等级的不断提高,气体绝缘变电站(GIS)在我国电力系统中的应用越来越广泛。
6) SF_6 gas insulation
SF6气体绝缘
1.
In this paper the application of GIS combined electric appliance(all-closed combined appliance with SF_6 gas insulation) is described.
本文概述了GIS组合电器(SF6气体绝缘全封闭组合电器)在山西华泽铝电有限公司电解铝厂的应用,并对GIS组合电器的结构、性能、及在电解铝厂应用的优点做了详细的分析。
补充资料:气体绝缘金属封闭开关设备绝缘试验
气体绝缘金属封闭开关设备绝缘试验
insulation test for gas insulated metal-enclosed switchgear
,在现场试验时感到很不方便。故多使用串联谐振装,尤其合适的是采用变L大置频式串联谐振装置作为高压电源进行试验。变频电源的频率可在50一30OHz间调节,以便在不同试品容量下,回路均能发生谐振。这类装置的优点是设备重量轻,噪声小,固定电抗器的设计制造容易。试一蓉可书图1变频式串联谐振试验装置T一供电变压器;L一电感;Cx一试品电容验表明,在上述频率范围内的耐压试验与工频耐压试验的结果是一致的。 此外,还可进行冲击耐压试验。振荡操作冲击耐压试验对发现污染和不正常电场结构均比较有效,适合于较高额定电压设备的耐压试验。试验可利用振荡操作冲击电压发生器进行,其原理接线和波形如图2所示。振荡频率可用250Hz或低于2.skHzo 图2振荡操作冲击电压发生器 (a)原理接线图;(b)振荡操作冲击电压波形 局部放电试验GIS在最高运行电压下,其内部不应发生局部放电。除在工厂需进行局部放电试验外,最好在现场试验时配合工频耐压试验同时检测其局部放电情况。GIS的局部放电一般采用加速度传感器来检测。其工作原理是通过检测局部放电引起的GIS壳体的微弱振动来实现对局部放电的测量。该试验可以检测出放电量为数十皮库至数百皮库的微弱放电。口lti丰日eV日口n日门引,u feno匕{伙团Qu门门g目e匕e{IUO丫uo门ShiVa门气体绝缘金属封闭开关设备绝缘试验(ins1)-lation testfor gasinsulated metal一enelosedsWltch卯ar)对气体绝缘金属封闭开关设备(简称为GIS)进行的绝缘性能检查试验。主要包括绝缘电阻试验、讨压试验、局部放电试验。 绝缘电阻试验用25 00V兆欧表测量其绝缘电阻,一般在整体组装完毕,而SF。气体未充人前进行。 耐压试验与其他电力设备不同,在GIS的现场试验中必须进行耐压试验,以检查其在出厂、运输和安装过程中是否混人导电杂质,部件有无位移或者装配不良等现象,避免因绝缘水平下降而在运行中造成事故、一般认为耐压试验可在交流电压下进行,它不仅可发现内部污染叻口导电微粒),还可对GIS作老炼试验二耐压试验的时间通常为王mi。,可采用逐级升压方式,即从较低电压开始,每级电压停留一段时间;若发生击年则可降低或去掉电压,进行分析后再重复进行,月的是对GIS做老炼试验,以消除一些可自行恢复的缺陷。由于GIS的电容量较大,如采用工频试验变压器作为高压电源来进行试验,则变压器的容量很