说明:双击或选中下面任意单词,将显示该词的音标、读音、翻译等;选中中文或多个词,将显示翻译。
您的位置:首页 -> 词典 -> 负序功率方向保护
1)  negative sequence power direction relay
负序功率方向保护
1.
On the basis of the analysis of sequence network and sequence components of shunt reactor turn-to-turn faults, a novel turn-to-turn fault protection, namely negative sequence power direction relay is proposed.
通过对并联电抗器的匝间故障、区内、区外接地故障以及由单相重合闸引起的非全相运行状态等情况的研究与仿真测试,表明负序功率方向保护不仅能在各种系统故障及运行情况下做出正确判断,更提高了对并联电抗器匝间故障保护的灵敏度。
2)  directional relay based on negative sequence power
故障分量负序功率方向保护
3)  negative sequence directional protection
负序方向保护
4)  negative power directional unit
负序功率方向
1.
To prevent this maloperation,negative power directional unit can be used for judging the fault between internal and external,which is a way to prevent turn-to-turn faults protection maloperat.
提出增加用负序功率方向元件来进行判断内外部故障,可以有效防止匝间保护误动作。
5)  directional power protection
功率方向保护
1.
The method of test on transformer s directional power protection;
变压器功率方向保护校验方法探讨
6)  zero-sequence(negative-sequence) direction protection
零序(负序)方向保护
补充资料:功率方向保护
      利用电压和电流的乘积判明电流流向(相位)的继电保护。用于多侧电源的系统。其主要元件是功率方向继电器,由电流互感器和电压互感器(见互感器)取得电流、电压信号,以判明短路故障位于保护装置处的正向或反向。功率方向继电器的接入必须十分注意电流、电压接线端子的极性,以免造成系统继电保护的大面积误动或拒动。
  
  用于相间短路的功率方向继电器,应采用90°接线方式,即A相继电器接夒Α和妧BC,余类推。这样可使两相短路时无电压死区(指无法保护的电压区段);正确选择继电器内角,可使三相短路时的电压死区最小。用于接地短路的功率方向继电器应接零序电流和零序电压,并特别注意正确接线方式是+3夒0和-3妧0(零序电压反极性)。
  
  并非所有多侧电源的保护都要装功率方向继电器。母线两侧的两相邻保护,其时限大者不必装设方向元件。若反向短路电流大于起动元件的动作值,也不需装设方向元件。
  

说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条