1) Voltage resonance
电压谐振
1.
This paper advises to establish a mathematical model which not adding to the power-factor compensation for the Gas Discharge Lamp and series voltage resonance for the Electronic Ballast of the fluorescent lamp.
建立气体放电灯不加功率因数补偿,荧光灯电子镇流器串联电压谐振的数学模型。
2.
By analyzing the voltage,current,voltage resonance and current resonance principle in the resonant earthed system,this paper presents the equivalent analysis models of the resonant earthed system.
本文通过对这种接地方式下电流、电压分布以及电压谐振和电流谐振原理的分 析,建立了相应的等值分析模型,指出了谐振接地方式能有效熄灭电弧的原理、消弧线圈调谐的原则,并提出了 基于可实时调节消弧线圈的谐振接地电网单相接地故障选线新方法,为提高谐振接地电网的单相接地故障保 护性能提供了研究基础。
3.
With theoretical analysis and practical calculation it is proved that the overvoltage phenomenon which appeared in the startup and adjustment process of Dongming switching station is a serial voltage resonance caused by the parameter mismatch.
文章通过实际计算和理论分析,证明了在东明开关站启动调试过程中出现的过电压现象是由系统参数设置不当而发生串联电压谐振引起的。
3) resonance voltage
谐振电压
4) resonant overvoltage
谐振过电压
1.
In the light of the analysis of the resonant overvoltage ,the causes of resonant overvoltage are found out ,and the methods to solve the problems are put forward,to ensure the safety and reliable operation of the power System.
通过对谐振过电压的分析,找出了谐振过电压的原因,提出了解决问题的方法,保证了电力系统的安全可靠运行。
2.
The RTDS was used to analyze and calculate the resonant overvoltage occurred during start-up debugging of 500 kV Ganshan-shuangsi double-circuit lines on the same tower,and the hidden troubles in various operational modes are studied.
应用实时数字仿真系统(RTDS)对500 kV阚山—双泗同塔双回线路启动调试中发生的异常谐振过电压进行了全面细致的仿真计算研究,列举了各种工况的仿真结果,对谐振原理进行了分析,对实际运行系统可能出现的各种运行方式所存在的安全隐患作了分析研究,提出了切合实际和可行的运行方案及建议。
5) resonance overvoltage
谐振过电压
1.
With the understanding of the generation of the resonant overvoltage and ferromagnetic resonance overvoltage limit,lightning arrester and the HXB arc-resonance extinguishing overvoltage protection installment are proposed to use.
了解谐振过电压的产生与对铁磁谐振过电压限制,建议采用避雷器与HXB型消弧及消谐过电压保护装置。
2.
As for the 1000kV AC pilot project in China, it is possible to appear resonance overvoltage with higher amplitude caused by energizing no-load transformers.
研究了我国1000kV特高压试验示范工程中可能出现幅值较高的合空载变压器谐振过电压现象,阐述了合空载变压器谐振过电压的机理与影响因素及其对策。
6) Piezoelectric Resonator Type
压电谐振式
1.
Study of Piezoelectric Resonator Type Force Sensor Respond Time;
压电谐振式力传感器响应时间的研究
补充资料:电力系统电压互感器谐振过电压
电力系统电压互感器谐振过电压
resonance overvoltage due to potential transformer in electric power system
南定理,可将三相对地电容等效连接在电撅变压器和互感器的两个中性点之间,由此着出,谐振属于零序性质。无论是电源合闸至空载母线所引起的电压互感器的涌流现象,还是线路中发生对地闪络和熄弧后C。中残余电荷经电压互感器放电所引起的磁饱和现象,都会在一定的C0值下激发起谐振过电压,它表现为电力系统中性点发生位移,并全部反映至开口三角形绕组,引起虚幻的接地故障信号。这是配电网中造成故障最多的一种内部过电压. 图1中性点不接地系统中三相电压 互感器接线图和等效谐振回路(a)三相电压互感导接线图;(b)等效谐振回路 由于谐振的零序性质,导线的相间电容、余弦电容器和传愉的三相有功负荷均对谐振不起作用。 随着C。的增加(即导线增长),将依次发生高频、工频和分频谐振。在很短的空母线合闸时,C0很小,会产生3倍以上的高频谐振过电压。较大的c0则会出现工频谐振过电压,此时一相对地电压很低,其它两相的对地电压接近于线电压,故工频谐振和单相接地现象往往难以区别。当母线上的出线较长时,C。很大将会发生分频谐振,其频率略低于电源颇率的一半,电压表的指针会发生低频摆动,谐振电压分t和开口三角形电压接近于相电压,由于此时谐振频率和相应的励磁感抗减半,互感器趋于深度磁饱和,励磁电流急剧增大,高达额定值的数十倍以至百倍以上,从而造成互感器的发热、喷油以至爆炸。在高频和分频谐振时,三相对地电压同时升高。 可以通过两种途径来抑制上述谐振现象.其一是采取阻尼吸能措施,即在开口三角形绕组两端临时并接一个低值电阻(在6一10kV小电网中,可用200~50ow的白炽灯泡)或将互感器高压中性点经大电阻接地。其二是破坏谐振条件,即人为地增大对地电容使之超过某一临界值,或将开口三角形绕组临时短接,或将互感器高压中性点临时不接地,或将电网改为通过消弧线圈接地。d旧nl一x一tongd旧nyo hugonq一x旧zhen guod{anyo电力系统电压互感公谐振过电压(resonanceovervoltage due to potential transformer inelectrie power system)电磁式电压互感器由于铁芯磁饱和引起的铁磁谐振过电压。在中性点不接地和直接接地电力系统中均有可能发生. 中性点不接地系统中电压互感器的谐振过电压图1中电源变压器的中性点不接地,电压互感器的中性点直接接地,其励磁电感La、L。和Lc分别与导线和母线的对地电容C。相并联而形成谐振回路。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。
参考词条