1)  single-phase autoreclosure
单相自动重合闸
1.
A novel method which uses the fault phase current characters of shunt reactors to identify permanent faults for single-phase autoreclosure on transmission lines is presented in this paper.
提出了一种基于超高压输电线路并联电抗器故障相电流特性的单相自动重合闸永久故障识别方法。
2)  single-phase auto-reclosure
单相自动重合闸
1.
For transmission lines with two shunt reactors,this paper presents a novel method of identifying permanent faults for single-phase auto-reclosure.
提出一种适用于两端带并联电抗器的超高压输电线路的单相自动重合闸永久故障识别方法。
3)  single-phase automatic reclosing
单相自动重合闸
1.
This paper presents a single-phase automatic reclosing method based on RBF neural network, and a three-layer RBF neural network model.
提出了基于RBF神经网络的单相自动重合闸的方案,将RBF神经网络用于其中,建立了一个三层前向网络模型 利用EMTP及MATLAB进行了大量的仿真实验,验证了其可行性,并克服了自适应单相重合闸的电压判据在判别瞬时性故障与永久性故障时存在的缺陷。
4)  three-pahse auto-reclosing
三相自动重合闸
5)  single and/or three phase autoreclosing
单相和/或三相自动重合闸
6)  intelligent adaptive single-phase automatic reclosing
智能式自适应单相自动重合闸
补充资料:自动重合闸
自动重合闸
auto-reclosing

   广泛应用于输电和供电线路上的有效反事故措施。即当线路出现故障,继电保护使断路器跳闸后,自动重合闸装置经短时间间隔后使断路器重新合上 。大多数情况下,线路故障(如雷击、风害等)是暂时性的,断路器跳闸后线路的绝缘性能(绝缘子和空气间隙)能得到恢复,再次重合能成功,这就提高了电力系统供电的可靠性。少数情况属永久性故障,自动重合闸装置不再动作,需查明原因,予以排除。一般情况下,线路故障跳闸后重合闸越快,效果越好。重合闸允许的最短间隔时间为0.15~0.5秒  。线路额定电压越高,绝缘去电离时间越长。自动重合闸的成功率依线路结构、电压等级、气象条件、主要故障类型等变化而定。据中国电力部门统计,一般可达60%~90%。用电部门的另一种广泛应用的反事故措施是备用电源自动投入,通常所需时间为0.2~0.5秒。它所需投资不多而维持正常供电带来的经济效益甚大。