1) connection between generator-transformer block and line
发变组-线路接线
2) generator-transformer-circuit unit wiring
发电机-变压器-线路组单元接线
1.
The paper analyzed some problems,such as breaker failure protection,non-whole phase protection,configuration of reclosing and five-protection lockout focusing on the characteristics of generator-transformer-circuit unit wiring,and proposed suggestions how to solve these problems in its design and operation.
针对发电机-变压器-线路组单元接线的特点,对其断路器失灵保护、非全相保护、重合闸配置、五防闭锁等问题进行了分析。
3) line-transformer-connection
线路变压器组接线
1.
Study and application on the operation program of the backup power switchover unit in the substations styling in line-transformer-connection;
线路变压器组接线变电所备用电源自投方案的研究与应用
4) generator-transformer-line band
发变线组
5) generator-transformer-line group
发-变-线组
6) line-transformer unit
线路-变压器组
1.
Study on relay protection of 220 kV line-transformer unit;
220 kV线路-变压器组的保护特点探讨
补充资料:变压器-线路组接线
变压器-线路组接线
transformer-line block scheme
b一a{lyo日一xlon{LJZLJ}lex{o!〕变压器一线路组接线(transformer一line bloekscheme)变压器和线路串联连接的接线方式。一001嗯(b)习阁般在主变压器高压侧装有断路器,见图(a)。也有高压侧不设断路器的,见图(b),但此时要考虑发电机或主变压器内部故障时能迅速切断对侧断路器。当线路对侧无电源时高压侧不装断路器,只装隔离开关,此时在发电机电压回路中一般要装断路器。当线路对侧有电源时为了节省断路器也可仅装隔离开关和人工接地开关,在发电机或变压器故障时利用人工接地开关快速合闸人为地造成线路接地短路,线路继电保护动作.使对侧断路器断开并停机,以切除发电机或变压器。本接线的优点是:①接线简单,设备少。②变压器一线路 组接线简图(a)高压侧设断路器;(b)高压侧不设断路器高压配电装置布置简单,占地面积小。缺点是:①线路故障或检修时,主变压器停运。②主变压器故障或检修时,线路停运。 这种接线适用于:①抽水蓄能电站;②没有近区负荷,将电能集中送至离电站较近的枢纽变电所或距离较近的梯级水电站或水电站群联合开关站的电站;③只有一台机组一回出线的电站;①电站初期发电时的过渡接线。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。