1) coupler
[英]['kʌplə] [美]['kʌplɚ]
母联
1.
Research of busbar protection s logic on dead-zone fault of coupler;
母线保护中母联死区故障保护逻辑的研究
2.
The article introduces two arithmetic of partial differential,and analyses the method of using compare the current vector of coupler breaker,and provides sampling arithmetic and vector arithmetic.
母线微机保护装置已发展的比较成熟,装置通用的选择故障母线的方法是利用总差动和分差动相配合;文中介绍了利用分差动选择故障母线时的两种算法,分析了利用母联电流方向比较元件选择故障母线的方法,并从瞬时值方面和向量值方面提供了两种算法。
3.
Automatic switching malfunction of 2245 coupler due to upper power source loss of Guang an 220 kV substation was discussed.
探讨了某次系统事故中,广安220kV变电站由于上一级电源失电,2245母联自投误动作,2245母联CSB-21A备自投装置由于采用可编程逻辑的设计思想,序列存在缺陷,未将“对侧母线无压”作为闭锁条件,导致2215、2216同时跳闸出口的相关问题,并结合实际运行经验,提出了一些观点。
2) bus differential and bus-coupler protections
母差母联
3) bus coupler malfunction
母联失灵
1.
This paper analyses problems existing in practice and corresponding improvement measures,points out the problem of adopting typical design for bus coupler malfunction protection when bus-bar or bus-coupler dead zone fault exists presently,and also enu.
在目前220 kV双母线接线的母线断路器失灵保护的设计中,存在以下几种特殊情况,即:线路故障时线路断路器失灵后分别出现主变断路器、母联断路器及出线断路器再失灵的连环失灵特殊情况,并分析了现场实践中存在的问题及改进措施,另外还提出目前存在母线或母联死区故障时母联失灵保护沿用典型设计存在的问题,列举了可以取消母联失灵外部启动回路的必要性。
2.
This paper introduced the configuration of 220kV microprocessor-based bus protection of Hunan power grid,analyzed interrelation among bus differential,bus coupler malfunction and breaker malfunction protections,and enumerated the necessity and feasibility of canceling external starting loop in bus-coupler malfunction and the unattached voltage blocking device RCS-918A.
介绍了湖南电网220kV母线保护的配置现状,分析了各种母差保护、母联断路器保护、失灵保护之间的配合关系及存在的问题,论证了取消母差与失灵保护间的二次回路、取消独立的复合电压闭锁装置RCS-918A的可行性和必要性,对充电时母联失灵和母联死区故障无保护的问题提出了改进措施。
4) bus-bar switch
母联开关
1.
The C phase of a 220kV circuit which was connected to the bus-bar failed,while after 140ms the bus-bar switched on abnormally.
最近浙江省某变电站发生一起220 kV母线全停事故,接于正母线运行的一条220 kV线路C相故障,切除故障后C相开关重燃引发正母差失灵保护动作,此后由于母联开关偷合造成220 kV副母差动动作以至220 kV母线全停。
2.
The present paper aims to solve the long-existing problem in Sanhe Power Plant that when the bus-bar switch is closed,the warning signal will show that AC circuit breaks and Bus Differential Protection exit is blocked.
针对三河发电有限责任公司长期以来存在的母联开关合闸后,出现交流断线报警信号,母线差动保护出口被闭锁这一问题,通过查阅和分析三河发电有限责任公司220 kV母线差动保护有关图纸和厂家资料,经过回路查线,校验继电器及试验录波和反复研究,确认了问题的根本原因,并制定了解决了方案,从而消除了由于设计问题(从动继电器使用不当)而存在的隐患。
5) bus-tie TA
母联TA
1.
The effect of the bus differential winding selection on the scope of bus protection in bus-tie TA;
母联TA中母差绕组的选择对母线保护范围的影响