1) high-voltage flameproof switch
高压隔爆开关
1.
Aiming at the existing problem of high-voltage flameproof switch in realizing integrated(protection),namely under influence of disturbance of decaying DC component,decaying DC component can not be filtered by traditional full wave Fourier algorithm,so that the protection will easily fail to operate or(unwanted) operate.
针对现有的高压隔爆开关在实现综合保护时存在的问题,即在衰减直流分量干扰的作用下,采用通用的全波傅氏算法无法滤除衰减直流分量,容易产生误动和拒动,文章提出了一种改进型全波傅氏算法,该算法能完全滤除衰减直流分量及高次谐波信号。
2) high-voltage explosion prevention switch
隔爆高压真空配电开关
1.
The improvement on integration of instruments for PB4 series high-voltage explosion prevention switch;
介绍PB4系列矿用隔爆高压真空配电开关综合保护改进过程,阐述了工作原理及改造过程。
3) HV explosion-proof switch for coalmine
矿用高压隔爆开关
4) explosion suppression switch
隔爆开关
5) high-voltage explosion-proof switch
高压防爆开关
1.
Design of the measurement and control system for the high-voltage explosion-proof switch based on double-CPU
基子双CPU控制的高压防爆开关测控系统的设计
6) HV disconnecting switch
高压隔离开关
1.
Malfunction analysis and countermeasure of HV disconnecting switch on type DJJ_1 power car;
DJJ_1型动力车高压隔离开关故障分析与对策
2.
HV disconnecting switches were severely damaged in historical big earth quakes,which are mainly caused by porcelain pole brittle failures.
在以往的大地震中,高压隔离开关均遭受了严重的损坏,此类设备的损坏主要由于瓷柱脆性破坏造成。
补充资料:高压开关电气与机械联动的可靠性比较
本文根据故障概率分布和机械联动与电气联动两种方式的优缺点比较,对采用电气及机械联动方式的高压断路器的可靠性进行了分析。
1 引言
高压断路器在电力系统中起控制和保护作用,其性能的可靠与否关系到电力系统的安全、稳定运行。为降低非全相分合闸情况出现,有的场所需要用三相机械联动。有的用户更直观地判断三相机械联动断路器可靠性远大于电气联动的断路器,但实际情况却需要具体分析。
2 断路器故障概率统计
据CIGRE于1988~1991年对1978~1991年投运的66kV及以上单压式SF6断路器进行的可靠性调查,共70708台年,因操动机构故障造成的失效占总失效数的64.8%,其中二次电气控制和辅助回路故障占21%,操动机构机械故障占43.8% 。
1989~1997年全国电力系统110、220、330kV和500kV SF6,断路器操动机构部分故障统计见表1。操动机构包括2个部分,一是机械传动部分;二是包括控制机械部分合、分操作的控制回路和辅助回路,如接线端子、接触器、辅助开关、分合闸线圈、微动开关、马达、气体继电器等二次元件。共统计故障458次,机构故障304次。
表1 1989~1997年全国电力系统110、220、330kV和500kV SF6断路器操作机构部分故障统计
上述统计资料表明,目前断路器主要故障为操动机构故障,且机械故障占有较大比例。