1) series compensating capacitance
串联补偿电容
1.
In view of the problems arising from the series compensating capacitance introduced into transmission lines and the influence on line protection,this paper analyzes the solvability of the model method,a protection algorithm for series-compensated transmission lines.
针对串联补偿电容接入输电线路后引发的问题及对线路保护工作的影响,对串联电容补偿线路的保护算法——模型法进行了可解性分析,指出该方法虽然具有简单直观的优点,但需要求解三阶线性方程组,并且仿真实验计算的结果与实际值存有较大误差,为此,提出了减少误差的方法——实用降阶法。
2) series capacitor compensation
串联电容补偿
1.
In this paper the selection scope of the reactance of series capacitor compensation in electrified railway is discussed based the equivalent calculation circuit of 27.
5kV侧电压损失计算电路为基础,对电气化铁道串联电容补偿装置容抗的选择范围进行了分析,对串补装置安装位置与最大提升网压的关系及其影响因素进行了研究,并对供电臂新设串补装置和新增串补装置的设置方案给出了建议。
2.
The technique of series capacitor compensation had been applied recently to improve transmission ability of power grid.
近年来,为了提高电网的输送能力,串联电容补偿技术被广泛采用。
3.
It s important to study the effect of series capacitor compensation on line protection.
研究串联电容补偿对线路保护的影响具有重要意义。
4) series compensation
串联电容补偿
1.
Both ultra-high-voltage (UHV) transmission technology and series compensation are effective measures to improve the transmission capability of transmission line and stability of power system.
特高压输电技术和串联电容补偿技术部是提高输电线路传输容量、改善电力系统稳定性的有效措施,同时又都给输电线路继电保护提出了新的更高的要求。
5) series capacitor compensation
串联电容器补偿
1.
For studying the transient process of series capacitor compensated high-voltage transmission network, the basic principle and functions of series capacitor compensation are expatiated firstly.
为了研究含有串联电容器补偿的高压输电网络的暂态过程,在阐述串联电容器补偿基本原理和作用的基础上,利用MATLAB中的电力系统模块库(PSB)和Simulink,建立了一个735kV串联电容器补偿输电网络的系统模型,并对其一相对地短路的暂态过程进行了仿真。
6) TCSC
可控串联电容补偿器
1.
STUDY ON NEGATIVE DAMPING CHARACTERISTIC OF TCSC;
可控串联电容补偿器的负阻尼特性研究
2.
The TCSC(Thyristor-Controlled Series Capacitor) installed in higher voltage lines can improve system transient stability and enhance transfer capability.
可控串联电容补偿器(TCSC)装设在高压线路上可改善系统的暂态稳定性,提高线路的传输容量。
3.
s:Based on the analysis of running mode,action after fault,dynamic power frequency impedance of TCSC(Thyristor-Controlled Series Capacitor) and compared with FSC(Fixed Series Compensation),the influence of TCSC on distance protection,direction component and pilot protection are analyzed.
在分析可控串联电容补偿器TCSC(Thyristor-ControlledSeriesCapacitor)的运行模式、故障后的动作行为和动态基频阻抗特点的基础上,对比常规串联电容补偿器FSC(FixedSeriesCompensa鄄tion),分析了TCSC对距离保护、方向元件及纵联保护的影响,认为:与FSC的线路相比,在TCSC线路上保护的性能不会降低,在FSC线路上运行的保护,可以在TCSC线路上很好地运行。
补充资料:串联电容补偿装置保护
串联电容补偿装置保护
Series capacitor/compensator protection
不装设MOV,只靠旁路间隙进行过电压保护,当线路故障电容器组两端的电压超过规定值时,旁路间隙放电,保护电容器组不受损害.其优点是节省投资便于扩建,缺点是区外故津后电容器组的再接入时间长。 电容器过负荷保护通常装在一相上。当过负荷的电流与持续时间超过电容器的额定过负荷能力时,保护动作使旁路断路器合上,将电容器退出. 电容器内部故障保护包括内部元件保护和桥式差动保护。电容器内部元件保护由装在外壳内每个元件上的单独熔丝构成,元件击穿时熔丝熔断将故障元件隔离。桥式差动保护由装在两申电容器中部连线上的电流互感器或传感器(见今联电容补偿装l中的图1)以及相应的继电保护组成,正常时连线两端电位平衡,无电流通过,当某些电容器元件击穿、熔丝熔断后,两端电压不平衡,保护动作.当不平衡程度较轻,电容器上的过电压不超过额定电压10%时,桥式差动保护一般只发信号;当击穿元件多、不平衡严重、电容器上的过电压超过额定电压10%时,桥式差动保护合上旁路断路器,将电容器退出。 金属氛化物限压器保护包括过载保护及损坏保护。过载保护一般由MOV电流、能t和温度测量等元件组成,当MOV过载时一般触发旁路间隙使其放电然后合上旁路开关,经过一段时间后,根据运行要求,再断开旁路开关将申联电容器再接人系统。当MOV保护装t监测到的MOV电流持续超过正常水平,或MOV电阻低于正常水平,就认为 MOV损坏,保护装t将旁路断路器快速闭合,申补电容退出运行。 旁路间隙保护一旦旁路间隙导通,旁路断路器随之将其暂时短接,当旁路间隙的绝缘强度恢复后或MOV经散热,热容t恢复后,根据运行要求旁路断路器可断开,申补装工重新投人运行。 旁路断路器故障保护一般旁路断路器都装有备用的合阿线圈以防合闸失灵。万一无法合闸,就将命令送至线路断路器,将线路断路器跳开,或者同时命令旁路筋离刀闸合上。 次同步谐振保护由对次谐波电流敏感的继电保护装t或模块组成。当发生次谐波谐振时.次谐波保护动作,合上旁路断路器,将电容器退出. 平台故库保护当申联电容补偿装置的任何一点对平台击穿或闪络时,该保护动作使旁路断路器合闸,将申联电容退出运行。平台上下通常用光纤来传递保护和控制信号。